Your current location:Home - Products
Products Characteristic:
1)Low frequency online ups, the three-phase input and three-phase output series
2)DSP digital control technology
Core system uses the world's most advanced all-digital DSP control technology, which can effectively guarantee the UPS' core system accurate, and fast running. The performance of UPS is more stable.
3)Advance IGBT inverted technology
Combined advanced IGBT technology with high frequency Pulse Width Modulation technique(PWM), It could reduce noise and power loss, to ensure users can load in a variety of working situations and obtain high-quality voltage output and maximum cost-effectiveness, but also make input efficiency more than 95%.
4)Advance phase-balanced technology
With most advanced phase-balanced technology now, it features best stability, even if loss-phase, it still operate at normal condition, especially in some worse power supply environment.
5)Super capacity of three-phase unbalance
UPS ensures the balance of three-phase voltage and phase when the three-phase input voltage or the 100% three-phase output load is unbalanced. and ensure the 100% three-phase unbalanced load continuous operation.
6)Design of advanced control architecture.
And the advanced modular design to reduce the average time to repair (MTTR), and the best maintenance .
7)Built-in isolation transformer
Built-in isolation transformer, To avoid disturbance input of external devices, the UPS has short circuit protection, and more strong overload capacity, also greatly improve the security and stability of the load.
8)Perfect battery management
Set the best charging current according to battery capacity, improve battery efficiency, extend battery lifespan.
9)The input characteristics of super
The UPS can be connected with the diesel generator power, fully meet the precision equipment large can work normally in the power supply mode of diesel generating sets.
10)Intelligent monitoring function
Through the RS232 interface or network adapter ( SNMP card ) to implement remote monitoring, display UPS working parameters on screen.
11)Advanced Redundant Parallel Connection technology.
Using the most advanced Redundant Parallel Connection technology, no additional control card, without the need for centralized control, eliminate single points of failure system, and only when the UPS output connection and control board communication connection, 8 UPS and machine operation.
Technical Specification
KT10K~120K
Model |
KT10KVA |
KT20KVA |
KT30KVA |
KT40KVA |
KT50KVA |
KT60KVA |
KT80KVA |
KT100KVA | |||
Battery voltage |
460~384VDC | ||||||||||
Efficiency |
≥95% | ||||||||||
Noise |
≤63dB (Distance |
≤65dB (Distance | |||||||||
Dimension W×D×H ( mm) |
550×760×1190 |
685×800×1450 |
1085×935×1650 | ||||||||
Weight(kg) |
210 |
260 |
320 |
350 |
460 |
490 |
550 |
780 | |||
KT120K~400K
Model |
KT120KVA |
KT150KVA |
KT160KVA |
KT200KVA |
KT300KVA |
KT400KVA |
Battery voltage |
460~384VDC |
480VDC | ||||
Efficiency |
≥96% |
≥98% | ||||
Noise |
≤65dB (Distance |
≤68dB (Distance | ||||
Dimension W×D×H ( mm) |
1250×935×1800 |
2000×935×1800 | ||||
Weight(kg) |
860 |
1150 |
1280 |
1600 |
2100 |
2500 |
General Parameters
INPUT | |
Voltage |
three phase with four lines and ground, 380V±25% |
Frequency |
50Hz/60Hz±10%(Automatically) |
Efficiency |
≥95% |
OUTPUT |
|
Voltage |
three phase with four lines, 380V±1% |
Frequency |
50HZ/60HZ±0.05%(Battery) |
Power factor |
0.8-1 |
Harmonic distortion |
linear load<3% Non-linear load<5% |
Imbalance voltage |
Balance load≤1% Imbalance load≤3% |
Phase shif angle |
Balance load≤±1° Imbalance load≤±2° |
Transient response |
Output at 0~50%~100% ≤5% response time≤10ms |
Wave form |
Pure sine wave |
Overload protection |
110%≥300 Min,125%≥10 Min,150%≥1 Min |
Crest factor |
3:1 |
BATTERY |
|
Charging time |
Charge to 90% in 8 hours |
Max charging current |
|
SYSTEM |
|
Transfer time |
0 ms |
MTBF |
300000 hours |
Communication |
RS232、SNMP(Optional) |
Safety rate |
IP21 |
Temperature |
-10~ |
Relative humidity |
0~93%(Non-condensing) |